Please read this guide carefully before installation. Please keep this manual in an accessible place for future reference. This manual should remain in the hands of the device owner.

security considerations
Please read these installation safety instructions carefully before installing an air conditioner. After the installation is complete, make sure the drive is working properly during the boot process. Instruct the customer in the operation and maintenance of the device. Advise customers to keep this installation manual with the user manual for future reference. Always use a licensed installer or contractor to install this product. Improper installation may result in water or refrigerant leakage, electric shock, fire, or explosion. Meaning of the symbols DANGER, WARNING, CAUTION and NOTE:

DAIKIN VRV air conditioning system instruction manual - Manuals+ (2)DANGER🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
DAIKIN VRV air conditioning system instruction manual - Manuals+ (3)RESERVATION🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
DAIKIN VRV air conditioning system instruction manual - Manuals+ (4)ATTENTION🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 🇧🇷 Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It can also be used to warn against unsafe practices.
DAIKIN VRV air conditioning system instruction manual - Manuals+ (5)TO USEIndicates situations that can only lead to accidents with damage to equipment or property.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (6)DANGER

  • The refrigerant gas is heavier than air and replaces oxygen. A massive leak will cause oxygen starvation, especially in basements, and a suffocation hazard will result in serious injury or death.
  • Do not ground the devices to water pipes, gas pipes, telephone wires, or lightning rods as incomplete grounding creates a serious risk of electrical shock which can result in serious injury or death. Also, grounding gas lines will result in gas leaks and possible explosion, which can result in serious injury or death.
  • If a refrigerant gas leak occurs during installation, ventilate the area immediately. The refrigerant gas will generate toxic gases if it comes into contact with fire. Contact with this gas will result in serious injury or death.
  • After completing the installation work, check that no refrigerant gas is leaking through the system.
  • Do not install the device in an area where combustible materials exist, as there is a risk of explosion which could result in serious injury or death.
  • Dispose of all packaging and shipping materials safely in accordance with federal/state/local laws or ordinances. Packing materials such as nails and other metal or wooden parts, including plastic packing materials, used for shipping can cause injury or death by suffocation.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (7)RESERVATION

  • Installation work may only be carried out by qualified personnel. The installation must be carried out according to these installation instructions. Incorrect installation may cause water leakage, electric shock, or fire.
  • When installing the unit in a small space, take measures to prevent the refrigerant concentration from exceeding the allowable safety limits. Excessive refrigerant leakage, possibly
    B. by an accident in a closed environmental space, can lead to oxygen deficiency.
  • Use only the specified accessories and parts for installation work. Failure to use the specified parts may result in water leakage, electric shock, fire, or the unit falling.
  • Install the air conditioner on a sufficiently strong base
    capable of supporting the weight of the device. Insufficient stability may cause the device to fall and cause injury.
  • Consider strong winds, typhoons or earthquakes when installing. Incorrect installation may cause the device to fall and cause accidents.
  • Please ensure that a separate circuit is available for this equipment and that all electrical work is performed by qualified personnel in accordance with local, state and national codes. Insufficient power supply capacity or improper electrical construction may cause electric shock or fire.
  • Ensure that all wiring is secure, that the specified cables are used and that there are no external forces on the terminal or cable connections. Incorrect connections or installations may cause a fire.
  • When wiring, arrange the wires so that the control box cover can be securely attached. Improper placement of the control box cover may result in electric shock, fire, or other damage
    Terminal overheating.
  • Switch off the device before touching electrical parts.
  • This device can be installed with a residual current device (GFCI). While this is an accepted measure of added protection, the floor system in North America does not require a dedicated GFCI.
  • Tighten the terminal cover of the device (panel) firmly. If the terminal cover/panel is not installed properly, dust or water may enter the outdoor unit and cause a fire or electric shock.
  • When installing or relocating the system, keep the refrigerant circuit free from substances other than the specified refrigerant (R410A), such as B. Air. Any presence of air or other foreign matter in the refrigerant circuit may cause abnormal pressure build-up or rupture, which could result in personal injury.
  • Do not change the settings of the protection devices. If the pressure switch, thermal switch or other protection device is short-circuited and forcibly operated, or if parts other than those specified by Daikin are used, it may cause a fire or explosion.
  • Do not install it in a humid room such as a bathroom or laundry room, as there is a risk of fire or electric shock.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (8)ATTENTION

  • Do not touch the switch with wet fingers. Touching a switch with wet fingers can cause electric shock.
  • Do not allow children to play in or around the device as they may be injured.
  • The fins of the heat exchanger are sharp enough to cut and
    can cause injury if used incorrectly. To avoid injury, wear gloves or cover ribs when working near them.
  • Do not touch the refrigerant piping during and immediately after operation because the refrigerant piping may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping, compressor and other parts of the refrigerant cycle. . This could result in burns or burns on your hands if you touch the refrigerant piping.
    To avoid injury, wait for the tubes to return to normal temperature or wear appropriate gloves if you must touch them.
  • Insulate the pipes to prevent condensation.
  • Be careful when transporting the product.
  • Do not turn off the power immediately after stopping operation. Always wait at least 5 minutes before disconnecting the power supply. Otherwise water may leak out.
  • Do not use a filling cylinder. Using a charging cylinder can cause refrigerant deterioration.
  • The R410A refrigerant in the system must be kept clean, dry and airtight.
    (a) Clean and dry: Foreign matter (including mineral oil such as SUNISO oil or moisture) must be prevented from entering the system.
    (b) Resistant: R410A contains no chlorine, does not deplete the ozone layer and does not reduce the earth's protection from harmful UV radiation. R410A may contribute to the greenhouse effect if released. Therefore, take suitable measures to check the refrigerant lines for leaks. Read the Refrigerant Lines chapter and follow the procedures.
  • Since R410A is a mixture, the additional refrigerant required must be filled in in liquid form. If the refrigerant is charged in a gaseous state, its composition may change and the system will not function properly.
  • The indoor unit is for R410A. Consult the catalog of indoor models that can be connected. Normal operation is not possible when connected to other devices.
  • Transmission of the handheld remote control (wireless kit).
    In rooms with electronic fluorescent lighting (inverter or quick-start type), the distance may be less than expected. Install the indoor unit away from fluorescent lamps such as
    as much as possible.
  • Indoor units are for indoor installation only. The outdoor units can be installed outside or inside. This device is intended for indoor use.
  • Do not install the air conditioner in the following places:
    (a) Where a mineral oil mist or oil mist or vapor occurs, for example in a kitchen. Plastic parts can deteriorate and fall off, allowing water to leak out.
    (b) Where corrosive gases such as B. sulfuric acid gas, are generated. Corroded copper tubing or soldered parts can cause refrigerant leakage.
    (c) Near machines that emit electromagnetic waves. Electromagnetic waves can disturb the operation of the control system and cause the device to malfunction.
    (d) Where flammable gas may leak, where carbon fiber or combustible dust is suspended in the air, or where volatile combustible materials such as paint thinner or gasoline are handled. Operating the device under these conditions may cause a fire.
  • Take appropriate measures to prevent small animals from using the outdoor unit as a shelter. Contact of small animals with electrical parts may cause malfunction, smoke or fire. Instruct the customer to keep the area around the device clean.
  • This device is not intended for use by persons (including children) with restricted physical, sensory or mental abilities or lack of experience and knowledge, unless they are supervised by a person responsible for their safety or have been instructed in the use of the device . . .

DAIKIN VRV air conditioning system instruction manual - Manuals+ (9)TO USE

  • Lay the power supply and transmission wiring for the indoor and outdoor units at least 1 m away from TVs or radios to avoid picture interference or noise. Depending on the radio waves, a distance of 1m may not be enough to eliminate noise.
  • Dismantling of the unit, treatment of refrigerant, oil and additional parts must be carried out in accordance with applicable local, state and national regulations.
  • Do not use the following tools used with conventional refrigerants: pressure gauge, charging hose, gas leak detector, check valve, refrigerant charging socket, vacuum gauge or refrigerant recovery equipment.
  • If conventional refrigerant and refrigerating machine oil are mixed in R410A, the refrigerant will deteriorate.
  • This air conditioner is a device that should not be available to the general public.
  • Since the design pressure is 4.0 MPa (580 psi), the wall thickness of the field installed piping must be selected in accordance with applicable local, state, and national codes.

Codes and Regulations
This product has been designed and manufactured in accordance with national regulations. Installation in accordance with these codes and/or applicable local codes/regulations is the responsibility of the installer. The manufacturer assumes no responsibility for equipment installed in violation of any law or regulation. The rated output is reached after 72 hours of operation.

The original instructions are written in English. All other languages ​​are translations of the original instructions.

contents disguise

11 BEFORE INSTALLATION

1.11-1 Precautions

1.21-2 Accessories

1.31-3 combination

1.41-4 Checklist

22 . CHOOSING THE INSTALLATION LOCATION

33 . PREPARATIONS BEFORE INSTALLATION

(Video) installing a DAIKIN VRV system...pt2...

44 . INSTALLING THE TWO DIAL UNIT

55 . REFRIGERANT PIPE

5.15-1 Pipe size selection

5.25-2 Precautions for pipe connection work

5.35-3 Pipe connection

5.45-4 Leak testing and vacuum drying

5.55-5 pipe insulation

66 . ELECTRICAL WIRING WORKS

6.16-1 General Instructions

6.26-2 Example of the overall system

6.36-3 Circuit, Safety Devices and Wiring Requirements

6.46-4 Wiring example

6.56-5 Wiring Connections

77 . FIRST ADJUSTMENT

7.17-1 Field Settings

(Video) DAIKIN VRV PIPING SYSTEM

88 . ADD AN EXTRA CHARGE OF REFRIGERANT

99 . CHECK OPERATION AND CHECK OPERATION

10 documents/resources

11 related posts

1 . BEFORE INSTALLATION

1-1 Precautions
  • Confirm in advance that the refrigerant used in the installation is R410A. The unit will not function properly with any other type of refrigerant.
  • If you move the unit during or after unpacking, secure it with the 4 hanging brackets and avoid applying force to other parts, especially the refrigerant piping and the control box.
  • For more information on installing external and internal drives, see the installation guide that came with each drive.
1-2 accessories
  • Check whether the following accessories are included in the package.

Important
Do not throw away any accessories that may be needed for the installation work until the installation is complete.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (10)

TO USE

  • You will need reducers (field supply) when the field pipe diameter as described in the outdoor unit installation manual or technical data book does not match the outdoor unit pipe diameter.
  • The thermal insulation of the connection lines on the outdoor unit side must be provided on site.
Combination 1-3
  • For the corresponding series of indoor and outdoor units, refer to the catalog or other documents.
  • Select the branch selection unit to set the total capacity (total unit capacity) of the downstream indoor units, refer to Table 1. About the capacity of the indoor units, refer to Table 2.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (11)

* The total capacity and number of indoor units connectable to each branch connection is up to 54 and 5, respectively. When the total capacity of indoor units to be connected downstream is more than 54 (MAX 96), use a connecting pipe kit (KHRP26A250T, sold separately) to connect two connections to be connected downstream of the bypass of the switching unit.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (12)

<Selection example> In the case of a branch select unit connected to an FXFQ12 and an FXMQ18.
Total Capacity = 12+18 = 30

1-4 Checklist

During the installation work, pay particular attention to the following points and check them again after the installation is complete:

Post-installation checklist

DAIKIN VRV air conditioning system instruction manual - Manuals+ (13)

Delivery Checklist
DAIKIN VRV air conditioning system instruction manual - Manuals+ (14)

two . CHOOSING THE INSTALLATION LOCATION

When selecting the mounting location, consider the following requirements and obtain customer approval:

  • The location must be able to support the weight of the branch selector.
  • The site must allow inspection openings to be installed on the side of the control box. (A separate opening is required when lowering the product.)
  • Sufficient space must be available for installation and maintenance work. (See Figure 1.)
  • The pipe length for the indoor unit and the outdoor unit must be equal to or less than the allowable pipe length (as specified in the installation manual attached to the outdoor unit).
  • Refrigerant flowing through the pipes can generate noise. Ensure that the necessary precautions are taken when installing in noise-sensitive applications.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (15)

(*1) Leave enough space to connect the field tubes.
(*2) This space is required to place the top plate when servicing the EV coil.
(*3) This space is required to remove the top plate when servicing the EV coil.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (16)RESERVATION
Install the device securely in a place that can support its weight. Insufficient force may cause the bypass switch unit to fall and cause injury.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (17)ATTENTION

  • Leave enough space in the control box for maintenance work.
  • To avoid video and audio interference, install the tap selector unit and associated power and transmission cables at least 1 m away from TVs and radios. Depending on the reception, however, interference can also occur when maintaining a minimum distance of 1 m.

3 . PREPARATIONS BEFORE INSTALLATION

Install the suspension bolts and suspension brackets as shown in the figure below.

  • Use a hanger bolt size of 3/8 inch. (M8) up to 7/16 inch. (M10).
  • Use molded inserts and countersunk foundation bolts for new installations, or hole anchor bolts or similar hardware for existing installations, and be sure the installation is such that it can support the weight of the unit.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (18)

Four . INSTALLING THE TWO DIAL UNIT

Only use accessories and parts that meet the specifications specified when the device was installed.

  1. Position the branch dial and lock it temporarily.
    Attach the hanging brackets to the hanging bolts as shown in the figure at right. Be sure to secure the nuts (3/8 inch (M8) or 7/16 inch (M10), 3 pieces in 4 places) and washers (for 3/8 inch (M8), 15/10 OD 16 inch.. (24 mm) to 1-1/8 inch (28 mm) or 7/16 inch (M10), OD 1-3/16 inch (30 mm) to 1-5/16 inch (34 mm): 2 pieces in 4 places ) (locally supplied) from the top and bottom of the hangers on either side of the unit to secure it.
  2. Adjust the height of the device as desired.
  3. Use a spirit level to verify that the unit is installed in a level orientation.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (19)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (20)RESERVATION

(Video) VRF/VRV HVAC Systems | Working principle and benefits | HVAC 11

  • Install the branch dial in a horizontal orientation. (Vertical installation is not permitted).
  • Install the nuts on the top and bottom of the hook brackets. If the bottom nut is overtightened without the top nut in place, the hook bracket and top plate may warp, causing the unit to make abnormal noises.

5 . REFRIGERANT PIPE

  • For instructions on how to install the piping between the outdoor unit and the bypass selection unit, how to select a refrigerant bypass kit and how to install the piping between the refrigerant bypass kit and the indoor units, refer to the installation manual attached to the external drive.
  • Before starting the work, make sure that the refrigerant used is R410A. (The unit will not work properly with any other type of refrigerant.)
  • Insulate all piping, including liquid lines, high/low pressure gas lines, suction gas lines, gas lines and piping connections to them. Failure to insulate these pipes could result in water leakage or burns. Low-temperature gas flows in particular in the high/low-pressure gas line in full cooling mode, so that the same amount of insulation is required as for the suction gas line. Besides, high-temperature gas flows in high/low-pressure gas pipes and gas lines, so please use insulation that can withstand more than 120°C (250°F).
  • Select the insulation material according to the installation environment. See the technical data book for more information. Otherwise, condensation may form on the surface of the insulation.
5-1 Tube Size Selection

Select the piping size between the outdoor unit (refrigerant branch kit) and branch selection unit and between the branch selection unit and indoor units (refrigerant branch kits) according to the connection examples 1 and 2 below and Tables 3, 4 and 5 .

DAIKIN VRV air conditioning system instruction manual - Manuals+ (21)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (22)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (23)DAIKIN VRV air conditioning system instruction manual - Manuals+ (24)

TO USE

  • If the number of indoor units to be connected is less than the number of sub-ports (there are empty sub-ports or you plan to increase the number in the future), any of the sub-ports may be left unused. Be sure to follow the correct procedure for closing unused ports.
  • If you plan to add new indoor units in the future, please select a pipe size based on the total capacity of the indoor unit before adding new units. Do not choose a pipe size based on future total capacity. This leads to abnormal operation. If the pipe size does not change before and after the lengthening, then the lengthening is acceptable.
  • For more information on expansion, please contact your Daikin sales representative.
5-2 Precautions for Piping Work

Connect the hoses.

  • Braze (*2) the refrigerant pipes after nitrogen replacement (replace the air with nitrogen while replacing the nitro
    flow into the refrigerant line (*1)). (See Fig. 2.) (*1) The pressure regulator for the nitrogen evolved during welding should be set at about 0.02 MPa (2.9 psi) (enough to feel a gentle breeze on your cheek).
    (*2) Do not use flux when brazing the refrigerant pipe.
    Use phosphorous copper (B-Cu93P-710/795: ISO 3677) for the brazing alloy, which does not require flux. (The use of chlorine flux may cause pipe corrosion, and if it contains fluorine, it may cause the coolant lubricant to deteriorate, which would adversely affect the coolant piping system.)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (25)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (26)ATTENTION

  • Do not use anti-rust agent when welding the pipe. (Residual residue may clog hoses or cause parts to malfunction.)
  • For more information about the refrigerant piping of the outdoor unit, refer to the installation manual attached to the outdoor unit or the technical data book. (Failure to purge the pipes or charge additional refrigerant may result in insufficient refrigerant volume in the pipes or other problems that cause the unit to malfunction [e.g. improper cooling or heating]).
5-3 pipe connection

DAIKIN VRV air conditioning system instruction manual - Manuals+ (27)

(*1) Displays field tube.
(*2) Reducers (field supply) may be required if local pipe size does not match the branch selector pipe size (Table 5).

If there are unused secondary ports (not connected to an indoor unit)

  • If there are unused bypass ports, use the locking tube (accessory (4)). If there are many unused branch connections, be sure to use an optional closed line kit (KHFP26A100C).
5-4 Leak Testing and Vacuum Drying
  • After completing the work on the refrigerant piping to the indoor units, bypass selection unit and outdoor unit, perform leak test and vacuum drying. For more information on the leak test pressure, refer to the installation manual of the outdoor unit.
5-5 pipe insulation
  • After completing the gas leak check, refer to the following figures and use the supplied insulating tube (accessory (2)) and clamps (accessory (1)) to attach the insulation.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (28)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (29)ATTENTION

  • Insulate all piping, including liquid lines, high/low pressure gas lines, suction gas lines, gas lines and piping connections to them. Failure to insulate these pipes could result in water leakage or burns. In high/low pressure gas lines in particular, low-temperature gas flows in full cooling mode, so that the same amount of insulation is required as for suction gas lines. Besides, high-temperature gas flows in high/low-pressure gas pipes and gas lines, so please use insulation that can withstand more than 120°C (250°F).
  • If you reinforce the insulating material according to the installation environment, also reinforce the insulation of the pipes protruding from the unit. The necessary insulating material for the reinforcement work must be provided on site. See Engineering Data Book for more information.
  • If the tape or clamps of the insulating material are tightened too much, the thickness of the insulating material will decrease and the insulating performance will deteriorate.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (30)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (31)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (32)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (33)ATTENTION

  • Roll up the insulation material with the seam facing up to prevent condensation from entering. (See Figure 3.)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (34)

6 ELECTRICAL WIRING WORK

6-1 General Instructions
  • All wiring must be performed by a licensed electrician.
  • All locally supplied parts and materials and electrical work must comply with local regulations.
  • Always ground the wires. (According to the national regulations of the relevant country).
  • Always turn off the power supply before performing electrical wiring work.
  • Follow the "WIRING DIAGRAM" attached to the control box cover to connect the outdoor unit and indoor units.
  • Properly connect the wire of the specified wire type and copper gauge. Also use the supplied clamp to avoid applying excessive force to the clamp (field wire, ground wire).
  • There must be a built-in disconnect switch in the hard wiring. Use a minimum 1/8 inch all pole circuit breaker. (3 mm) between contact point gaps.
  • Make sure that the ground wire does not touch gas pipes, water pipes, lightning rods, or telephone ground wires.
    • Gas lines: Gas leaks can cause explosions and fires.
    • Water lines: cannot be grounded when using hard vinyl line.
    • Grounding Telephones and Lightning Rods: The ground potential during lightning strikes is extremely high.
  • A circuit breaker capable of disconnecting power to the entire system must be installed.
  • This system consists of several branch selection units. Mark each branch selection unit as unit A, unit B 🇧🇷 🇧🇷 and make sure the symbols on the terminal blocks of the outdoor unit and the indoor unit match correctly. If the wiring and piping between the outdoor unit, branch selection unit and indoor unit are not compatible, the system may not work properly.
  • Do not switch on the power supply (bypass switch, circuit breaker) until all other work has been completed.
6-2 Example of the overall system

DAIKIN VRV air conditioning system instruction manual - Manuals+ (35)

6-3 Circuit Safety Devices and Wiring Requirements
  • A circuit (see Table 6) must be provided for connecting the device. The circuit must be protected with safety devices in accordance with local and national regulations, ie with a fuse, circuit breaker or GFCI.
  • When using RCDs, be sure to use a 30mA rated residual current at high speed (0.1 seconds or less).
  • Use only copper conductors.
  • Use insulated power cords.
  • Select the type and size of power cord in accordance with relevant local and national codes.
  • Use 18-16 AWG (two-wire) vinyl-coated cable or wire for transmission wiring. The transmission cable lengths are as follows: Between branch selector and indoor units: max. 1000m (3280ft) Between branch selector and outdoor unit: max. 1,000m (3,280ft) Between branch selector units: max. 1,000m (3,280ft)
    Total cable length: 2,000 m (6,560 ft) or less

DAIKIN VRV air conditioning system instruction manual - Manuals+ (36)

TO USE

  • Table 6 of electrical characteristics above relates to a tap selector unit.
6-4 Wiring Example

DAIKIN VRV air conditioning system instruction manual - Manuals+ (37)RESERVATION
Install circuit protection safety devices in accordance with local and national codes. Failure to install circuit protection safety devices in accordance with local and national codes may result in electric shock or fire.

  • Below is an example of transmission wiring.
  • Connect the “TO IN/D UNIT (F1, F2)” terminals on the outdoor unit PCB to the “OUTDOOR UNIT (F1, F2)” terminals on the first branch selection unit.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (38)

TO USE

  1. Connect the cooling only unit to the “BS UNIT (F1, F2)” terminals of the last unit of the bypass selector.
  2. This wiring example is applied by connecting branch terminals C and D and connecting to the indoor unit. The terminal block to which the transmission wires are connected can be connected to either indoor unit C or indoor unit D. However, the DIP switches must be set correctly. For details on setting the DIP switches, see “7 . INITIAL SETTING".
  3. The maximum number of indoor units connected to one branch connection is 5.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (39)ATTENTION

  • Please use 2-wire transmission line. Using the same cable with 3 or more cores to connect 2 or more indoor units may cause them to stop with an error.
  • When using a shielded cable, be sure to ground one end of the shielded cable. Total cable length is 1500 m (4920 ft) when shielded cable is used.
  • Be sure to use ring terminals with insulating sleeves to connect the wires to the power terminal block. (See Figure 4.)

    DAIKIN VRV air conditioning system instruction manual - Manuals+ (40)

  • Do not use if the power terminal block and ground terminal are connected to the wiring of another circuit.
  • Do not pre-solder stranded wires.
  • Connect the wires securely so that the terminals are not subject to external forces.
  • Use an appropriately sized screwdriver to tighten the terminal screws. Using a screwdriver that is too small can damage the screw head and prevent proper seating.
  • Overtightening the terminal screws can damage the screw. For tightening torques of the clamping screws see table.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (41)

  • Never connect the power supply cables to the connection block for the transmission cables. This can damage the entire system.
  • A daisy chain configuration is required for transmission wiring. The transmission wiring cannot be branched again after the initial branch. (See Figure 5.)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (42)

6-5 Wiring Connections

DAIKIN VRV air conditioning system instruction manual - Manuals+ (43)

  • Transmission wiring Remove the control box cover and connect the wiring to the transmission wiring connectors (outdoor unit F1 and F2, branch selector unit F1 and F2 and each indoor unit (e.g. for BS12Q54TAVJ, indoor unit A to L) (F1 and F2 )) .
    At this time, pass the cables through the cable hole to the unit and use the supplied clamp (accessory (1)) to secure the cables. See the figure below for more information on how much insulation to remove from transmission cables.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (44)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (45)ATTENTIONCheck if the piping is consistent with the transmission wiring.

(Video) Daikin VRV Monitor Mode

DAIKIN VRV air conditioning system instruction manual - Manuals+ (46)

  • Power supply wire and ground wire Remove the control box cover and connect the power supply wire to the power supply terminal block (X1M). Also connect the ground wire to the ground wire clamp. Pass the power supply wires and ground wires together through the grommet (left) to the control box and use the supplied clamp (accessory (1)) to fix the wires securely. Be sure to connect the ground wire so that it comes out of the slot in the washer. (This may result in poor contact of the ground wire, resulting in the wire not functioning as a ground.)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (47)

DAIKIN VRV air conditioning system instruction manual - Manuals+ (48)RESERVATION
Arrange the wiring and reattach the control box cover securely. Pinched wires or a loose control box cover can cause electric shock or fire.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (49)ATTENTION

  • To hold the cable, use the supplied clamp (accessory (1)) to avoid pulling the cable connection, and then clamp the cable. After completing the wiring, also arrange the wiring so that the control box cover does not come off, and then reattach the control box cover properly. Be careful not to pinch the wires when replacing the control box cover. Always use the grommet to protect the cables.
  • Do not route transmission cables and power cables in the same places and keep them at least 2 inches apart outside the device. (50mm). Otherwise, the transmission wiring may pick up electrical noise (external noise) and cause a malfunction or breakage.
  • After completing the wiring work, use a sealant (locally procured) to seal the conduit hole. (Intrusion of small animals, etc. may cause interference.)
  • As shown in the figure on the right, wrap the transmission wiring between each branch dialing unit and the indoor unit with masking tape (locally supplied).

DAIKIN VRV air conditioning system instruction manual - Manuals+ (50)

7 . FIRST ADJUSTMENT

7-1 Adjustments in the field

Follow the instructions below to set the DIP switches as required.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (51)RESERVATION
Electric shock hazard! Before performing any work, be sure to disconnect all power sources connected to the device.

procedure

  1. Disconnect the power supply.
  2. Set the DIP switches (DS1, DS2) for the corresponding branch ports according to the table below.
  3. When the work is finished, be sure to close the control box cover.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (52)

<Settings>

  1. Setting for secondary ports where no indoor unit is connected

    DAIKIN VRV air conditioning system instruction manual - Manuals+ (53)

  2. Configuration when connecting branch ports

DAIKIN VRV air conditioning system instruction manual - Manuals+ (54)

8 ADD EXTRA COOLANT

Follow the instructions in the installation manual that comes with the outdoor unit to add an extra charge of refrigerant.

9 CHECK OPERATION AND TEST OPERATION

  1. Make sure the control box cover snaps back onto the control box.
  2. Please refer to the installation manual that comes with the outdoor unit and check and test.
    after all work on branch selection device, outdoor and indoor unit is completed and the operational safety of the devices is confirmed.
    • You will hear the motorized valve operate for about 90 seconds as it initializes (closes) automatically after power up, but this is not a problem.
    •System errors can be checked using the following methods: Remote control display General system errors, including the branch dial unit, can be identified using the LCD display on the remote control. For more information on the fault display and what it means, see the installation manual that comes with the outdoor unit.

DAIKIN MANUFACTURING COMPANY, L.P.
Technologiepark Daikin Texas,
Kermier Strasse 19001,
Waller, Texas, 77484, EE. UU.

DAIKIN VRV air conditioning system instruction manual - Manuals+ (55)

3P405106-12C EM20A009 [2105] AT

Documents/Resources

DAIKIN VRV air conditioning[pdf] Instruction Manual
BS4Q54TAVJ, BS10Q54TAVJ, BS12Q54TAVJ, VRV Air Conditioner

related posts

  • SHARP Air Conditioner Owner's Manual

  • air conditioning service manual

    Air Conditioner Service Manual - Download [Optimized] Air Conditioner Service Manual - Download

  • AIRFIX SAW001 climate support manual

    AIR CONDITIONER HOLDER AIR CONDITIONER HOLDER It must be installed by specialized professionals who…

  • Hisense air conditioner user menu

    (Video) DAIKIN VRV BASIC WIRING

    Hisense Air Conditioner User Menu - Download [Optimized] Hisense Air Conditioner User Menu - Download

FAQs

How do I check my Daikin error code? ›

How do I find my Daikin fault code? To find the source of your AC issue, hold down the “Cancel” button on your remote while pointing it to your indoor unit for about 5 seconds until the screen on your remote says “00”. Once this appears, keep clicking cancel and different codes will appear on the screen.

What are the three modes in Daikin AC? ›

  • • Press the MODE button to select the type of operating mode.
  • • For cooling only unit, the available modes are: COOL ( ), DRY ( ) and.
  • FAN ( ).
  • • For heat pump unit, the available modes are: AUTO ( ), COOL ( ), DRY ( ),
  • FAN ( ) and HEAT ( ).
  • • The AUTO ( ) mode is unavailable for chilled water system.

How do I reset Daikin control panel? ›

  1. (1) After cleaning, connect the power cord to AC outlet or turn on the circuit breaker.
  2. (2) With the air conditioner in non-operation, press and hold the filter cleaning indicator (LED) reset button for about 2 seconds.

What is the best setting for a Daikin air conditioner? ›

The ideal temperature setting of around 21-22°C all year round, enables your unit to work as efficiently as possible. Also, with most Daikin units, you can set a timer so the heat comes on automatically when you really need it to (so you can basically forget about adjusting it).

Which mode is best for cooling in Daikin AC? ›

Ideally, you should use Daikin's Cool Mode if the humidity and temperature levels are high. It would also be advisable to use this mode if you want to maintain a consistently cool temperature in your home.

How do you troubleshoot Daikin? ›

Daikin aircon troubleshooting—the full list
  1. If the on/off button is off.
  2. If the operation lamp is flashing (green flashing light)
  3. Double check the temperature on your remote.
  4. Check that the air filters are clean.
  5. Check that the air con is clear of obstructions.
  6. Check your doors and windows.
  7. Check that the sensor is working.

What is the problem if Daikin AC light is blinking? ›

The blinking light on your Daikin aircon may be indicative of low refrigerant levels. However, refrigerant does not easily 'run out,' evaporate, or get used up, so low refrigerant levels almost always means there's a leak in your air conditioner.

How do I check system error codes? ›

More ways to find an error code
  1. Use the Microsoft Error Lookup Tool.
  2. Install the Debugging Tools for Windows, load a memory dump file, and then run the ! err <code> command.
  3. Search the Microsoft Protocols site for the raw text or error code. For more information, see [MS-ERREF]: Windows Error Codes.
Feb 7, 2022

Which AC mode to use in summer? ›

In general, air conditioners work best in cooling mode when the temperature is set between 22°c to 24°c with a medium or high fan speed setting. You can change it according to your preferences at any given moment, but the efficiency may be impacted negatively.

Why is my Daikin AC not cooling? ›

the most common reason why your split and window Daikin Aircon is not cooling is because of unclean air filters. If the Aircon filter is unclean or clogged with dust and dirt, it might result in various problems. It must interfere with the proper working of the thermostat.

Can I use dry mode all day? ›

Dry mode will not remove 100% of the moisture in the air. Instead, it will help lower the humidity to a healthy level. However, it's recommended not to run your AC on dry mode for more than 1-2 hours at a time to avoid drying the air too much.

How do I reset my Daikin VRV? ›

Re: Daikin VRV3 master reset to default

Power down the outdoor from the isolator and then power up the outdoor. Press and hold the reset button on the outdoor PCB for around 20 seconds.

How do I reset my AC control board? ›

How to Reset an Air Conditioner
  1. Power down your AC. Start at your circuit breaker panel and flip the breaker that powers your AC. ...
  2. Find the button. Most air conditioning units are equipped with a reset button. ...
  3. Hold down the reset button for 3 to 5 seconds and then release.
  4. Restore power to your AC.

How do I reset my remote control? ›

For Android TVs released in 2015 or later, symptoms may improve by updating the software of the remote control.
...
Reset the remote control.
  1. Open the battery compartment cover and remove the batteries.
  2. Press and hold the Power button for three seconds.
  3. Insert the batteries again and close the battery compartment cover.
Feb 13, 2022

Which AC mode is best for cooling? ›

Essentially, the purpose of the “dry” function mode is to reduce the excess humidity or moisture in the air, and the cooling effect comes from the removal of that excess moisture.

What temperature is best for summer? ›

It turns out that the best indoor temperature for your home during the summer months is 78 degrees, according to the U.S. Department of Energy. If that temperature falls outside your comfort level, there are several ways to modify how your home feels without causing your energy bill to spike.

What is the best cooling temperature in AC? ›

Technical analysis indicates that, in order to achieve the desired comfort level at a steady state, the temperature setting can be 24-25 degree celsius.

Should AC be on auto or cool mode? ›

We recommend setting your thermostat to AUTO for the best balance of energy efficiency and comfort. If you are concerned about indoor air quality or suffer from allergies, the ON setting's increased air filtration could be beneficial.

How do I troubleshoot my AC problems? ›

Try the following DIY AC troubleshooting tips the next time you're having AC issues:
  1. Check for a dirty air filter.
  2. Check your thermostat settings.
  3. Check your air conditioner circuit breakers.
  4. Check your outdoor unit.
  5. Check all air vents.
May 31, 2017

How do I troubleshoot my AC unit? ›

Possible Solutions:
  1. Check the thermostat to make sure it's working properly.
  2. Take a look at the condenser to see if it's dirty or blocked. ...
  3. Clean and/or change your filter (We recommend once a quarter.)
  4. See if any ice has formed on the coils. ...
  5. Check and/or clean the outdoor compressor.
Aug 31, 2017

What are the troubleshooting steps in HVAC? ›

9 HVAC Troubleshooting Tips
  1. Make Sure Your HVAC System Gas Power. ...
  2. Try Resetting Your HVAC System. ...
  3. Make Sure Your Furnace Door is Closed. ...
  4. Check the Thermostat for Issues. ...
  5. Install a New Filter in Your Furnace or AC. ...
  6. Check all Vents for Obstructions. ...
  7. Turn off the AC. ...
  8. Check Furnace and AC Wires.
Mar 26, 2020

What causes lights to blink when air conditioner comes on? ›

This is because your AC requires a large amount of electricity to initially start up. When it starts, it temporarily drains power from other appliances like your lights, causing them to flicker slightly.

How do I stop my AC from blinking? ›

Sometimes, the blinking light is time-based and is a signal that the unit is due servicing. In this case, just ensure that the filters are cleaned and checked. If a deep cleaning is required then you can contact a trained professional to perform a chemical cleaning or overhaul.

Why is my AC blinking and not working? ›

Usually, having an air conditioner light blinking means something is wrong with the unit. It typically indicates some error occurring with operation as the sensor is detecting it. Many of the different brands in the marketplace have an indicator that will blink when the unit requires repair.

What are the system errors? ›

A system error occurs when a job request encounters a technical error from which it cannot recover, but otherwise exits of its own volition. Alternatively, a system error occurs when the server or operating system running the job crashes.

What are the reasons for system error? ›

2. Analysis of Causes of System Failure:
  • 2.1 Poor development practices. ...
  • 2.2 Incorrect assumptions with regard to system requirements. ...
  • 2.3 Poor user interface. ...
  • 2.4 Faulty hardware. ...
  • 2.5 Inadequate user training/ user error. ...
  • 2.6 Poor fit between systems and organisation. ...
  • 3.1 Poor development practices.

How do I stop stop code error? ›

General troubleshooting steps
  1. Review the stop error code that you find in the event logs. ...
  2. Make sure that you install the latest Windows updates, cumulative updates, and rollup updates. ...
  3. Make sure that the BIOS and firmware are up-to-date.
  4. Run any relevant hardware and memory tests.
Sep 2, 2022

Should AC fan be on auto or on in summer? ›

Keeping your fan on AUTO is the most energy-efficient option. The fan only runs when the system is on and not continuously. There is better dehumidification in your home during the summer months. When your fan is set to AUTO, moisture from cold cooling coils can drip and be drained outside.

Is 72 a good temperature for air conditioning? ›

When setting your thermostat, most homeowners find 72 is a good temperature for air conditioning. However, you may need to adjust that setting based on weather conditions. The bigger the difference between indoor and outdoor temperatures, the higher your energy bill will be.

Which AC mode is best for humidity? ›

However, during monsoons humidity level sometimes extends the recommended range. Therefore, it is advisable to run your AC in dry mode. Dry mode helps in extracting moisture thereby removing extra humidity from the environment.

Why does my air conditioner turn on but not cooling? ›

If your air conditioner will turn on, and your thermostat is set properly, but your system is not cooling you may have a dirty or blocked air condenser. Your first step is to check the outside unit and clean around and remove any debris or weeds that are blocking air circulation.

What is the common problem of Daikin air conditioner? ›

The system makes strange noises. Air conditioner not turning off due to wiring issues. Daikin ducted not cooling. Daikin ac unit leaking water.

What to check if AC is not cooling? ›

The following are a few things to check when your air conditioner is not cooling your space.
  1. Check and reset the thermostat. ...
  2. Replace the dirty filter. ...
  3. Clear the clogged condensation drain. ...
  4. Try to diagnose duct malfunctions. ...
  5. Clear the area around the compressor. ...
  6. Clean dirty coils.
Jan 24, 2022

What is dry mode on Daikin? ›

DRY operation eliminates humidity while maintaining the indoor temperature as much as possible. It automatically controls temperature and airflow rate, so manual adjustment of these functions are not available.

When should you not use dry mode? ›

We recommend using dry mode when it might be raining, damp and sticky inside and not that cold, but it's too cool to want to run the a/c on cooling mode. Dry Mode won't perform well on a hot summer's day. We recommend using cooling mode.

Is Dry mode better than cool mode? ›

“Cool mode” should be used during hot and dry seasons, while the aircon “dry mode” is more appropriate for humid seasons that aren't necessary hot and warm in temperature. Utilizing dry mode more often is also better for the environment.

How do I reset my AC without a reset button? ›

How do you reset your AC unit?
  1. Turn off your air conditioning system using the thermostat. ...
  2. Search for the breaker box. ...
  3. Shut off your AC unit at the breaker. ...
  4. Wait at least a full minute before switching the breaker back to the “on” position.
  5. Wait for 30 minutes before turning your unit back on at the thermostat.
Sep 10, 2021

What does an AC reset switch look like? ›

Some air conditioning systems have a reset switch, which is a small, red button. Typically, the button will be on the outdoor unit. If you have a problem locating it on the outdoor unit, you may find relevant details on the equipment's manufacturer's manual. Press the red button for three seconds and release.

How long does it take for an AC unit to reset? ›

After you've turned the system back on, it will take a bit of time for the air conditioner's internal circuitry to reset. It usually takes about 30 minutes, so sit tight until then.

Can you factory reset remote? ›

You can use Android Device Manager to remotely lock your device, erase everything on it, or change the lock screen passcode. Touch the box next to “Allow remote lock and factory reset.” When the “Activate device administrator” screen appears, read the text and touch Activate to turn on the device administrator.

What causes remote control to stop working? ›

There are a number of reasons why your remote may not be working. The most common are physical damage, battery issues, pairing issues, or issues with the infrared sensor on the remote or TV.

What are the symbols in Daikin AC remote? ›

Cool, Heat, Vent, Fan, Dry or Auto

The words “Cool”, “Heat”, “Vent”, “Fan”, “Dry” or “Auto” are displayed to present the Operation Mode. The Airflow Rate (Airflow level/Fan Speed) symbol is displayed to show the airflow rate that is set for the indoor unit.

How do I use Daikin smart control? ›

3 Simple Unit Pairing Steps
  1. Download GO DAIKIN App.
  2. Scan QR code to pair AC unit to smartphone.
  3. That's it! You can now control your AC from your smartphone.

What are the modes on a Daikin remote? ›

There are four modes on your controller:
  • COOL operation for cooling.
  • HEAT operation for heating.
  • AUTO operation selects an appropriate operation mode (COOL or HEAT) based on the indoor temperature and starts the operation.
  • DRY operation eliminates humidity while maintaining the indoor temperature as much as possible.

How can I increase my AC cooling by remote? ›

The temperature buttons are usually up and down arrows with TEMP written by them. Pressing the UP button will increase the set temperature and pressing the DOWN button will decrease the temperature. Most units have a MODE button which will cycle through the air conditioning units' different operations.

Videos

1. VRV VRF & Mini Split Air Conditioner - AC Training
(HVAC TIME)
2. DAIKIN VRV PIPE SIZING II VRF II DAIKIN
(Learn HVAC)
3. DAIKIN VRV FAULT ! *IT WONT WORK IN HEATING MODE !?
(HVAC UK)
4. Daikin - animated operation manual - FTXS20-25K
(DaikinEurope)
5. VRV Installation Training Part 1
(Daikin South Africa)
6. Daikin VRV S High Seasonal Efficiency Series (4-9HP) [DAIKIN]
(Daikin Industries, Ltd. [Official Channel])

References

Top Articles
Latest Posts
Article information

Author: Maia Crooks Jr

Last Updated: 04/08/2023

Views: 5725

Rating: 4.2 / 5 (43 voted)

Reviews: 90% of readers found this page helpful

Author information

Name: Maia Crooks Jr

Birthday: 1997-09-21

Address: 93119 Joseph Street, Peggyfurt, NC 11582

Phone: +2983088926881

Job: Principal Design Liaison

Hobby: Web surfing, Skiing, role-playing games, Sketching, Polo, Sewing, Genealogy

Introduction: My name is Maia Crooks Jr, I am a homely, joyous, shiny, successful, hilarious, thoughtful, joyous person who loves writing and wants to share my knowledge and understanding with you.